basic unit
Kampmann TOP unit heater for wall- or ceiling-mounting. Housing made of sendzimir galvanised sheet steel with standard suspension lugs, complete with motor guard and louvre, single-row, additional discharge and intake components can be screwed on. LABS compliant according to VDMA 24364, category A1/B1/B2/C1/C2-L and B1/C1/C2-W. Life Cycle Assessment (LCA) data is published in the form of an EPD according to EN 15804 and is available to download from the International EPD System. Registered in the building products platform DGNB Navigator. GWP (phase A1-A3), kg CO2 Äq.1,36E+02. Further calculations possible online.
Heat exchanger
High-output heat exchanger, steel with ellipse-shaped core pipe with steel fins, galvanised, suitable for LPHW and thermal oil.
| System | | 2-pipe |
| Max. operating pressure | bar | 16 |
| Max. entering water temperature | °C | 120 |
| Max. air inlet temp. | °C | 40 |
| Max. glycol volume | % | 50 |
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Overtemperature protection of the fan by active temperature management. Integrated motor protection.
Control
- With frost protection thermostat and connecting frame, fitted, temperature range -10/12 deg. C, 3 m capillary tube, sensor monitoring. Fitted within unit.
- With an external connection box.
Configuration
| Model size | | 4 |
| Width | mm | 540 |
| Height | mm | 500 |
| Length | mm | 320 |
| Weight | kg | 61.8 |
| Water content | l | 6.1 |
| Connection | | 1'' |