Basic unit
Kampmann KaCool D AF ceiling cassette for the air conditioning of rooms with suspended ceilings. Optimised AtmosFeel air opening to minimise draughts. Basic unit made of sendzimir galvanised sheet steel, partially insulated with a vapour diffusion and noise-reducing layer to prevent the ingress of condensation.
Optional primary air connection for the introduction of preconditioned outside air. Stylish panel in RAL 9016 traffic white. 4-sided air outlet through manually adjustable louvres.
Heat exchanger
High-output heat exchanger made of round copper pipes with aluminium fins, including anti-twist mechanism. Integrated air vent option.
| System | | 4-pipe |
| Max. operating pressure | bar | 8 |
| Max. entering water temperature | °C | 75 |
| Min. entering water temperature | °C | 6 |
| Max. air inlet temp. | °C | 30 |
| Max. glycol volume | % | 50 |
condensate drain
Condensate tray designed as an independent component that can be removed for cleaning and maintenance in accordance with VDI 6022.
Factory-fitted condensate pump including alarm contact for shut-down and notification. Material of condensate tray ABS
| max. delivery height | mm | 600 |
| Power consumption of condensate pump | W | 8.0 |
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Integral thermal contact. Motor fault: Automatic motor shut-off in the event of a fault. No fault message possible.
Insulation class F
Control
KaControl C1 control system factory fitted and wired. Controlled via a separate operating unit in the room as a master unit or for use as a slave unit.
Room control for up to six devices via KaController, expandable to up to 30 devices via CANbus interface (CANbus card required)
- Slot for optional interfaces:
- CANbus/Modbus/KNX card
- Temperature measurement optionally via sensor in the room control unit or external room temperature sensor
- One digital input configurable for:
- Device On/Off
- Comfort/Economy mode switch
- Heating/Cooling changeover
- Window contact, presence detector contact
- Card reader contact
- Output for the continuous (0-100%) control of the EC fan Night mode (energy-saving mode) that can be activated via a timer program in the KaController or room frost control activated via digital input. Five-stage fan control 1-2-3-4-5 Demand--led automatic fan mode with continuous (0-100 %) fan control, switch-off in the event of a fault.
Configuration
| Model size | | 4 |
| System | | 4-pipe |
| Air inlet | | ISO Coarse filter |
| panel | | with panel |
| Valve version | | without 2-way valve |
| Width (body) | mm | 570 |
| Length (body) | mm | 572 |
| Height (body) | mm | 286 |
| Width (Casing panels) | mm | 680 |
| Length (panel) | mm | 680 |
| Height (aperture) | mm | 40 |
Required suspended ceiling height | mm | 296 |
| Weight | kg | 27.8 |
| output voltage | V | 230 |
| frequency | Hz | 50 |
| Connection | | 1/2 inch |
| connection description | | female thread |