basic unit
Kampmann KaCool D AF ceiling cassette for the air conditioning of rooms with suspended ceilings. Optimised AtmosFeel air opening to minimise draughts. Basic unit made of sendzimir galvanised sheet steel, partially insulated with a vapour diffusion and noise-reducing layer to prevent the ingress of condensation.
Optional primary air connection for introducing pre-conditioned outdoor air. Stylish panel in RAL 9016 traffic white. 4-sided air outlet through manually adjustable louvres.
Life Cycle Assessment (LCA) data is published in the form of an EPD according to EN 15804 and is available to download from the International EPD System. Registered in the building products platform DGNB Navigator. GWP (phase A1-A3), kg CO2 Äq.1,47E+02. Further calculations possible online.
Heat exchanger
High-output heat exchanger made of round copper pipes with aluminium fins, including anti-twist mechanism. Integrated air vent option.
| System | | 4-pipe |
| Max. operating pressure | bar | 8 |
| Max. entering water temperature | °C | 75 |
| Min. entering water temperature | °C | 6 |
| Max. air inlet temp. | °C | 30 |
| Max. glycol volume | % | 50 |
condensate drain
Condensate tray designed as an independent component that can be removed for cleaning and maintenance in accordance with VDI 6022.
Factory-fitted condensate pump including alarm contact for shut-down and notification. Material of condensate tray ABS
| max. delivery height | mm | 600 |
| Power consumption of condensate pump | W | 8.0 |
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Integral thermal contact. Motor fault: Automatic motor shut-off in the event of a fault. No fault message possible.
Insulation class F
Control
The unit includes an infra-red receiver, and infra-red control unit and a wall bracket, enabling the unit to be controlled wirelessly.
The following functions are possible:
- On/Off
- temperature selection (setpoint specification)
- Fan speed (3-stage manual or automatic)
- mode (cooling, heating, recirculation, automatic)
- timer program
- In addition, the circuit board enables communication via a master slave circuit of the units (max. 30 units per operating unit).
Configuration
| Model size | | 2 |
| System | | 4-pipe |
| Air inlet | | ISO Coarse filter |
| panel | | with panel |
| Valve version | | without 2-way valve |
| Width (cabinet) | mm | 570 |
| Length (Body) | mm | 572 |
| Height (Cabinet) | mm | 286 |
| Width (panel) | mm | 680 |
| Length (Panel) | mm | 680 |
| Height (panel) | mm | 40 |
Required suspended ceiling height | mm | 296 |
| Weight | kg | 27.1 |
| output voltage | V | 230 |
| frequency | Hz | 50 |
| Connection | | 1/2 inch |
| connection description | | female thread |