Basic unit
Kampmann TOP unit heater for wall- or ceiling-mounting. Housing made of sendzimir galvanised sheet steel with standard suspension lugs, complete with motor guard and louvre, single-row, additional discharge and intake components can be screwed on. LABS compliant according to VDMA 24364, category A1/B1/B2/C1/C2-L and B1/C1/C2-W.
Heat exchanger
High-output heat exchanger, steel with ellipse-shaped core pipe with steel fins, galvanised, suitable for LPHW and thermal oil.
| System | | 2-pipe |
| Max. operating pressure | bar | 16 |
| Max. entering water temperature | °C | 120 |
| Max. air inlet temp. | °C | 40 |
| Max. glycol volume | % | 50 |
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Overtemperature protection of the fan by active temperature management. Integrated motor protection.
Control
- Built-in KaControl MC controller for continuous fan control with motor monitoring.
- For the control of 24 V DC actuators (Open/Closed) for heating and cooling operation.
- With connection option for 5 multifunctional inputs (room temperature, window contact, supply and return temperature, heating/cooling changeover, condensate alarm, sequential control via a 0-10 V signal etc.), unit-specific control and regulation algorithms with the core functions of room temperature control (heating/cooling).
- Timer program with battery-backed real-time clock for four operating modes (Day/Eco/Extra/Off), commissioning function.
- Grouping of up to 10 units and a display to create a control zone using CAN-bus, automatic addressing and communication monitoring of all bus subscribers, continuous synchronisation of all statuses and parameters within the group.
- CAN bus interface and galvanically isolated RS485 interface, each with two terminal blocks for separate connection with daisy chain cabling with a switchable terminal resistor.
- connection of central functions, such as heating cooling changeover to a freely selectable unit within the group.
- Ethernet interface with two RJ45 sockets with built-in switching function.
- KNX-TP interface with socket terminal, all terminals are designed as plugs, wireless communication via Wi-Fi web server for user-friendly operation and for complete password-protected parametrisation.
- protocols can be unlocked via licences: BACnet/IP, Modbus TCP, Modbus RTU, KNX.
- Repair switch which can be locked off using a lock on site.
- With an external connection box.
Configuration
| Model size | | 7 |
| Width | mm | 840 |
| Height | mm | 800 |
| Length | mm | 360 |
| Weight | kg | 192.8 |
| Water content | l | 16.8 |
| Connection | | 1 1/2'' |