Basic unit
Kampmann TOP unit heater for wall- or ceiling-mounting. Housing made of sendzimir galvanised sheet steel with standard suspension lugs, complete with motor guard and louvre, single-row, additional discharge and intake components can be screwed on. LABS compliant according to VDMA 24364, category A1/B1/B2/C1/C2-L and B1/C1/C2-W.
Heat exchanger
High-output heat exchanger, steel with ellipse-shaped core pipe with steel fins, galvanised, suitable for LPHW and thermal oil.
| System | | 2-pipe |
| Max. operating pressure | bar | 16 |
| Max. entering water temperature | °C | 120 |
| Max. air inlet temp. | °C | 40 |
| Max. glycol volume | % | 50 |
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Overtemperature protection of the fan by active temperature management. Integrated motor protection.
Control
KaControl recirculation air module
factory-fitted and wired ready for connection, consisting of:
- Repair switch which can be locked off using a lock on site.
- Mains adapter board, power supply terminals, plug-in, 230 VAC including dual protective conductor for looping through.
- Grey plastic housing, IP 54 rated, dimensions W x H x D: 230 x 140 x 125 mm
- KaControl PCB, specifications:
- Screw-in/plug-in terminals for connection of 24 VDC power supply
- tLAN interface for1 master and 5 slaves broadcast networks
- Slot for optional interface cards:
- RS485 (Modbus, CAN bus, KNX, for integration into BMS or DDC systems)
- Interface parameter programming key
- 2 digital inputs
- Freely parametrisable, e.g. for Day/Night changeover
- Window contact, configured as spring-loaded terminals
- 3 multifunctional inputs parametrisable as:
- Digital input (refer to previous point for functions)
- Analogue input passive for room, return air, coil or changeover sensor
- Active analogue input (0-10 VDC) for external specification of fan speed, configured as spring-loaded terminals
- Screw/plug-in terminals for connection of thermoelectric valve drives, 24 V DC, normally closed
- 1 analogue output 0-10 V DC for fan actuation
- Potentiometer for fan speed limitation
- DIP switch for basic setting of the application.
- Unit shut-down in the event of a fault with message via the control unit
- Uploading of control parameters via a service tool
- Temperature curves can be recorded via server connection
- test process to check inputs and outputs
- With an external connection box.
Configuration
| Model size | | 7 |
| Width | mm | 840 |
| Height | mm | 800 |
| Length | mm | 360 |
| Weight | kg | 161.4 |
| Water content | l | 16.8 |
| Connection | | 1 1/2'' |