Basic unit
Kampmann Venkon XL fan coil for cooling and/or heating. Designed for recirculation air applications with particularly high cooling and external pressure requirements. Designed as a recirculating air version with rectangular duct connection on the intake and discharge side. Hygiene-certified in line with VDI 6022. Sendzimir galvanised sheet steel housing. Wall-mounted unit (also suitable for ceiling mounting)
Filter classFilter ePM10>50% (M5).
Life Cycle Assessment (LCA) data is published in the form of an EPD according to EN 15804 and is available to download from the International EPD System. Registered in the building products platform DGNB Navigator. GWP (phase A1-A3), kg CO2 Äq.2,74E+02. Further calculations possible online.
Heat exchanger
High-efficiency heat exchanger made of round copper tubes with aluminium fins, including anti-torsion device to prevent damage to the coil.
| System | | 2-pipe |
| Max. operating pressure | bar | 10 |
| Max. entering water temperature | °C | 90 |
| Min. entering water temperature | °C | 5 |
| Max. air inlet temp. | °C | 25 |
| Max. glycol volume | % | 50 |
Condensate tray
Condensate tray, galvanised sheet steel, powder-coated and glued on all sides with thick insulation. Condensate tray designed as an independent component that can be removed for cleaning and maintenance in accordance with VDI 6022.
Fan
Double-sided suction radial fan. Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Integrated motor protection. Insulation class F.
Control
- Built-in KaControl MC controller for continuous fan control with motor monitoring.
- For the control of 24 V DC actuators (Open/Closed) for heating and cooling operation.
- With connection option for 5 multifunctional inputs (room temperature, window contact, supply and return temperature, heating/cooling changeover, condensate alarm, sequential control via a 0-10 V signal etc.), unit-specific control and regulation algorithms with the core functions of room temperature control (heating/cooling).
- Timer program with battery-backed real-time clock for four operating modes (Day/Eco/Extra/Off), commissioning function.
- Grouping of up to 10 units and a display to create a control zone using CAN-bus, automatic addressing and communication monitoring of all bus subscribers, continuous synchronisation of all statuses and parameters within the group.
- CAN bus interface and galvanically isolated RS485 interface, each with two terminal blocks for separate connection with daisy chain cabling with a switchable terminal resistor.
- connection of central functions, such as heating cooling changeover to a freely selectable unit within the group.
- Ethernet interface with two RJ45 sockets with built-in switching function.
- KNX-TP interface with socket terminal, all terminals are designed as plugs, wireless communication via Wi-Fi web server for user-friendly operation and for complete password-protected parametrisation.
- protocols can be unlocked via licences: BACnet/IP, Modbus TCP, Modbus RTU, KNX.
Connection
Female NPT thread includes factory-fitted adapters to 3/4 inch R-thread
Configuration
| System | | 2-pipe |
| Water connections | | right |
| Nominal voltage | V | 230 |
| Model size | | 3 |
| Length | mm | 262 |
| Width | mm | 1486 |
| Height | mm | 650 |
| Weight | kg | 57.1 |