basic unit
Kampmann KaCool D HY hygienic ceiling fan coil cassette for the air conditioning of rooms with suspended ceilings and exacting hygiene requirements. Hygiene-compliant according to VDI 6022 (Hygiene requirements governing ventilation systems and units) through the HYBETA hygiene institute.
Basic unit made of sendzimir galvanised sheet steel, partially insulated with a vapour diffusion and noise-reducing layer to prevent the ingress of condensation. A two-section aesthetic metal panel in RAL 9016 (traffic white) consisting of a lower frame and a visible panel is supplied separately. With a folding panel for cleaning and maintenance. Filter ePM10>50% (M5)
Heat exchanger
High-output heat exchanger, consisting of round copper tubes with aluminium fins, suitable for use with LPHW. Venting screws on the connection provide for simple and clean venting during commissioning.
| System | | 4-pipe |
| Max. operating pressure | bar | 8 |
| Max. entering water temperature | °C | 75 |
| Min. entering water temperature | °C | 6 |
| Max. air inlet temp. | °C | 35 |
| Max. glycol volume | % | 50 |
Condensate tray
Stainless steel built-in condensate tray with a gradient on all sides with a free outlet for the complete discharge of condensate. Condensate tray designed as an independent component that can be removed for cleaning and maintenance in accordance with VDI 6022.
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired.
Control
KaControl C1 control system factory fitted and wired. Controlled via a separate operating unit in the room as a master unit or for use as a slave unit.
Room control for up to six devices via KaController, expandable to up to 30 devices via CANbus interface (CANbus card required)
- Slot for optional interfaces:
- CANbus/Modbus/KNX card
- Temperature measurement optionally via sensor in the room control unit or external room temperature sensor
- One digital input configurable for:
- Device On/Off
- Comfort/Economy mode switch
- Heating/Cooling changeover
- Window contact, presence detector contact
- Card reader contact
- Output for the continuous (0-100%) control of the EC fan Night mode (energy-saving mode) that can be activated via a timer program in the KaController or room frost control activated via digital input. Five-stage fan control 1-2-3-4-5 Demand--led automatic fan mode with continuous (0-100 %) fan control, switch-off in the event of a fault.
Configuration
| Model size | | 4 |
| Filter class | | Filter ePM10>50% (M5) |
| Width (cabinet) | mm | 575 |
| Length (Body) | mm | 575 |
| Height (Cabinet) | mm | 385 |
| Width (panel) | mm | 600 |
| Length (Panel) | mm | 600 |
| Height (panel) | mm | 42 |
| Weight | kg | 36.7 |
| output voltage | V | 230 |
| frequency | Hz | 50 |
| Connection | | |
| | female thread |