basic unit
Kampmann TOP unit heater for wall- or ceiling-mounting. Housing made of sendzimir galvanised sheet steel with standard suspension lugs, complete with motor guard and louvre, single-row, additional discharge and intake components can be screwed on. LABS compliant according to VDMA 24364, category A1/B1/B2/C1/C2-L and B1/C1/C2-W. Life Cycle Assessment (LCA) data is published in the form of an EPD according to EN 15804 and is available to download from the International EPD System. Registered in the building products platform DGNB Navigator. GWP (phase A1-A3), kg CO2 Äq.3,59E+02. Further calculations possible online.
Heat exchanger
High-output heat exchanger, steel with ellipse-shaped core pipe with steel fins, galvanised, suitable for LPHW and thermal oil.
| System | | 2-pipe |
| Max. operating pressure | bar | 16 |
| Max. entering water temperature | °C | 120 |
| Max. air inlet temp. | °C | 40 |
| Max. glycol volume | % | 50 |
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Overtemperature protection of the fan by active temperature management. Integrated motor protection.
Control
KaControl recirculation air module
factory-fitted and wired ready for connection, consisting of:
- Repair switch which can be locked off using a lock on site.
- Mains adapter board, power supply terminals, plug-in, 230 VAC including dual protective conductor for looping through.
- Grey plastic housing, IP 54 rated, dimensions W x H x D: 230 x 140 x 125 mm
- KaControl PCB, specifications:
- Screw-in/plug-in terminals for connection of 24 VDC power supply
- tLAN interface for1 master and 5 slaves broadcast networks
- Slot for optional interface cards:
- RS485 (Modbus, CAN bus, KNX, for integration into BMS or DDC systems)
- Interface parameter programming key
- 2 digital inputs
- Freely parametrisable, e.g. for Day/Night changeover
- Window contact, configured as spring-loaded terminals
- 3 multifunctional inputs parametrisable as:
- Digital input (refer to previous point for functions)
- Analogue input passive for room, return air, coil or changeover sensor
- Active analogue input (0-10 VDC) for external specification of fan speed, configured as spring-loaded terminals
- Screw/plug-in terminals for connection of thermoelectric valve drives, 24 V DC, normally closed
- 1 analogue output 0-10 V DC for fan actuation
- Potentiometer for fan speed limitation
- DIP switch for basic setting of the application.
- Unit shut-down in the event of a fault with message via the control unit
- Uploading of control parameters via a service tool
- Temperature curves can be recorded via server connection
- test process to check inputs and outputs
- With an external connection box.
Configuration
| Model size | | 7 |
| Width | mm | 840 |
| Height | mm | 800 |
| Length | mm | 360 |
| Weight | kg | 132.8 |
| Water content | l | 16.8 |
| Connection | | 1 1/2'' |