basic unit
Kampmann TOP unit heater for wall- or ceiling-mounting. Housing made of sendzimir galvanised sheet steel with standard suspension lugs, complete with motor guard and louvre, single-row, additional discharge and intake components can be screwed on. LABS compliant according to VDMA 24364, category A1/B1/B2/C1/C2-L and B1/C1/C2-W. Life Cycle Assessment (LCA) data is published in the form of an EPD according to EN 15804 and is available to download from the International EPD System. Registered in the building products platform DGNB Navigator. GWP (phase A1-A3), kg CO2 Äq.3,59E+02. Further calculations possible online.
Heat exchanger
High-output heat exchanger, consisting of round copper tubes with aluminium fins, suitable for use with LPHW.
| System | | 2-pipe |
| Max. operating pressure | bar | 16 |
| Max. entering water temperature | °C | 120 |
| Max. air inlet temp. | °C | 40 |
| Max. glycol volume | % | 50 |
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Overtemperature protection of the fan by active temperature management. Integrated motor protection.
Control
- Frost protection thermostat, connecting frame and repair switch, fitted. Frost protection thermostat temperature range is -10 to 12°C, with a 3 m capillary tube and sensor monitoring, fitted within the unit. The repair switch is used for shutting down motors with thermal cut-outs, and connection of parallel units is possible. Thermal cut-outs must be linked beforehand and must open afterwards. Protection class is IP 55.
- With an external connection box.
Configuration
| Model size | | 7 |
| Width | mm | 840 |
| Height | mm | 800 |
| Length | mm | 360 |
| Weight | kg | 62.1 |
| Water content | l | 6.2 |
| Connection | | 1 1/2'' |