Basic unit
Kampmann Venkon fan coil for heating and/or cooling. Designed for rooms with high demands in terms of low noise emission and cosy room comfort. Hygiene-certified in line with VDI 6022.
Basic unit made of sendzimir galvanised sheet steel, insulated with a vapour diffusion and noise-reducing layer to prevent the ingress of condensation.
| Insulation thickness | mm | 3 |
| Air inlet | | Filter ePM10>50% (M5) |
Optional primary air connection for the introduction of preconditioned air.
Life Cycle Assessment (LCA) data is published in the form of an EPD according to EN 15804 and is available to download from the International EPD System. Registered in the building products platform DGNB Navigator. GWP (phase A1-A3), kg CO2 Äq.3.07E+02. Further calculations possible online.
Heat exchanger
High-output heat exchanger made of round copper pipes with aluminium fins, including anti-twist mechanism. Integrated air vent option.
| System | | 4-pipe |
| Max. operating pressure | bar | 10 |
| Max. entering water temperature | °C | 90 |
| Min. entering water temperature | °C | 4 |
| Max. air inlet temp. | °C | 40 |
| Max. glycol volume | % | 50 |
Condensate tray
Powder-coated galvanised sheet steel condensate tray. Condensate tray designed as an independent component that can be removed for cleaning and maintenance in accordance with VDI 6022.
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Insulation class F
Control
- Built-in KaControl MC controller for continuous fan control with motor monitoring.
- For the control of 24 V DC actuators (Open/Closed) for heating and cooling operation.
- With connection option for 5 multifunctional inputs (room temperature, window contact, supply and return temperature, heating/cooling changeover, condensate alarm, sequential control via a 0-10 V signal etc.), unit-specific control and regulation algorithms with the core functions of room temperature control (heating/cooling).
- Timer program with battery-backed real-time clock for four operating modes (Day/Eco/Extra/Off), commissioning function.
- Grouping of up to 10 units and a display to create a control zone using CAN-bus, automatic addressing and communication monitoring of all bus subscribers, continuous synchronisation of all statuses and parameters within the group.
- CAN bus interface and galvanically isolated RS485 interface, each with two terminal blocks for separate connection with daisy chain cabling with a switchable terminal resistor.
- connection of central functions, such as heating cooling changeover to a freely selectable unit within the group.
- Ethernet interface with two RJ45 sockets with built-in switching function.
- KNX-TP interface with socket terminal, all terminals are designed as plugs, wireless communication via Wi-Fi web server for user-friendly operation and for complete password-protected parametrisation.
- protocols can be unlocked via licences: BACnet/IP, Modbus TCP, Modbus RTU, KNX.
Configuration
| System | | 4-pipe |
| Air inlet | | bottom |
| Model size | | 67 |
| Length | mm | 1838 |
| Width | mm | 223 |
| Height | mm | 519 |
| Weight | kg | 46.4 |
| Water connections | | left |
| Connection Cooling | | 3/4'' |
| Connection Heating | | 1/2 inch |