Basic unit
Kampmann KaCool D AF ceiling cassette for the air conditioning of rooms with suspended ceilings. Optimised AtmosFeel air opening to minimise draughts. Basic unit made of sendzimir galvanised sheet steel, partially insulated with a vapour diffusion and noise-reducing layer to prevent the ingress of condensation.
Optional primary air connection for the introduction of preconditioned outside air. No panel included, must be ordered separately as an accessory.
Heat exchanger
High-output heat exchanger made of round copper pipes with aluminium fins, including anti-twist mechanism. Integrated air vent option.
| System | | 2-pipe |
| Max. operating pressure | bar | 8 |
| Max. entering water temperature | °C | 75 |
| Min. entering water temperature | °C | 6 |
| Max. air inlet temp. | °C | 30 |
| Max. glycol volume | % | 50 |
condensate drain
Condensate tray designed as an independent component that can be removed for cleaning and maintenance in accordance with VDI 6022.
Factory-fitted condensate pump including alarm contact for shut-down and notification. Material of condensate tray ABS
| max. delivery height | mm | 600 |
| Power consumption of condensate pump | W | 8.0 |
Fan
Energy-saving EC fan with 0-10 V input for continuously variable speed control. All rotating parts have low-noise and maintenance-free bearings. Factory-wired. Integral thermal contact. Motor fault: Automatic motor shut-off in the event of a fault. No fault message possible.
Insulation class F
Control
KaControl C1 control system factory fitted and wired. Controlled via a separate operating unit in the room as a master unit or for use as a slave unit.
Room control for up to six devices via KaController, expandable to up to 30 devices via CANbus interface (CANbus card required)
- Slot for optional interfaces:
- CANbus/Modbus/KNX card
- Temperature measurement optionally via sensor in the room control unit or external room temperature sensor
- One digital input configurable for:
- Device On/Off
- Comfort/Economy mode switch
- Heating/Cooling changeover
- Window contact, presence detector contact
- Card reader contact
- Output for the continuous (0-100%) control of the EC fan Night mode (energy-saving mode) that can be activated via a timer program in the KaController or room frost control activated via digital input. Five-stage fan control 1-2-3-4-5 Demand--led automatic fan mode with continuous (0-100 %) fan control, switch-off in the event of a fault.
Configuration
| Model size | | 2 |
| System | | 2-pipe |
| Air inlet | | ISO Coarse filter |
| panel | | without panel |
| Valve version | | without 2-way valve |
| Width (body) | mm | 570 |
| Length (body) | mm | 572 |
| Height (body) | mm | 286 |
| Width (Casing panels) | mm | 680 |
| Length (panel) | mm | 680 |
| Height (aperture) | mm | 40 |
Required suspended ceiling height | mm | 296 |
| Weight | kg | 23.8 |
| output voltage | V | 230 |
| frequency | Hz | 50 |
| Connection | | 3/4'' |
| connection description | | female thread |